Bell Sports Air Conditioner PQRY P72 96TGMU A User Manual

Air-Conditioners For Building Application  
HEAT SOURCE UNIT  
PQRY-P72·96TGMU-A  
For use with R410A  
INSTALLATION MANUAL  
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.  
MANUEL D’INSTALLATION  
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.  
 
8.2  
8
[Fig. 8.2.1]  
C
D
g
A
A
D
A
b
B
b
C
C
No.7  
a
a
A : BC controller (standard)  
B : BC controller (main)  
C : BC controller (sub)  
D : indoor unit (06 ~ 54)  
E : indoor unit (72, 96)  
B
B
D
D
E
D
c
c
d
No.1  
e
d
e
No.1  
f
No.2  
No.2  
D
D
D
D
D
D
E
No.3 No.4  
No.3 No.4  
No.5  
No.5  
No.6  
A
B
(Unit: mm [in])  
C, D  
(Unit: mm [in])  
Å Heat source model  
ı High press. side  
ø15.88 [5/8]  
Ç Low press. side  
ø19.05 [3/4]  
Ì High press.  
gas pipe  
Ó Low press.  
¬ Liquid pipe  
P72  
P96  
gas pipe  
ø19.05 [3/4]  
ø22.2 [7/8]  
ø19.05 [3/4]  
ø22.2 [7/8]  
~ 72  
73 ~ 108  
109 ~ 126  
ø15.88 [5/8]  
ø19.05 [3/4]  
ø19.05 [3/4]  
ø9.52 [3/8]  
ø12.7 [1/2]  
ø12.7 [1/2]  
(Unit: mm [in])  
Ï Gas line  
ø28.58 [1-1/8]  
Î Total capacity of indoor units  
Liquid line  
ø9.52 [3/8]  
ø9.52 [3/8]  
a, b, c, d, e, f, g  
Ô Model number  
(Unit: mm [in])  
Ï Gas line  
~ 54  
ø15.88 [5/8]  
ø19.05 [3/4]  
Liquid line  
55 ~ 72  
06,08,12,15,18  
ø6.35 [1/4]  
ø9.52 [3/8]  
ø9.52 [3/8]  
ø9.52 [3/8]  
ø12.7 [1/2]  
24,27,30,36,48,54  
ø15.88 [5/8]  
ø19.05 [3/4]  
ø22.2 [7/8]  
72  
96  
9.2  
9
[Fig. 9.2.1]  
[Fig. 9.2.2]  
<A> [Ball valve (Low press. side/flanged type)]  
<B> [Ball valve  
(High press. side/flared type)]  
<C> This figure shows the valve  
in the fully open state.  
A
3
E
E
B
O
S
1
B
G
O
S
A : Close-packed packing  
B : Hollow packing  
A
C
F
H
D
J
I
[Fig. 9.2.3]  
K
A: Valve stem  
B: Stopper pin  
H: Flare nut  
I: ø15.88 [5/8] (PQRY-P72)  
ø19.05 [3/4] (PQRY-P96)  
C: Packing (Accessory)  
J: ø19.05 [3/4] (PQRY-P72)  
D: Connecting pipe (Accessory)  
E: Open (Operate slowly)  
F: Cap  
ø22.2 [7/8] (PQRY-P96)  
K: Field piping  
G: Service port  
3
 
9.3  
[Fig. 9.3.1]  
[Fig. 9.3.2]  
D
A : Nitrogen gas  
B : To indoor unit  
C : System analyzer  
D : Lo knob  
A : System analyzer  
B : Lo knob  
F
N
E
F
B
B
G
H
C : Hi knob  
D : Ball valve  
O
A
E : Hi knob  
E : Low press. pipe  
F : High press. pipe  
G : Service port  
H : Three-way joint  
I : Valve  
I
HI  
LO  
C
HI  
G
LO  
B
C
F : Ball valve  
A
D
E
J
G : Low press. pipe  
H : High press. pipe  
I : Heat source unit  
J : Service port  
I
H
M
K
J : Valve  
[Fig. 9.3.3]  
K : R410A cylinder  
L : Scale  
J
L
M : Vacuum pump  
N : To indoor unit  
O : Heat source unit  
A
A : Syphon pipe  
B
In case of the cylinder having no syphon pipe.  
9.4  
[Fig. 9.4.1]  
[Fig. 9.4.2]  
[Fig. 9.4.3]  
B
A
C
B
A
C
D
E
E
E
A
B
D
A : Steel wire  
E
D
B : Piping  
C : Asphaltic oily mastic or asphalt  
D : Heat insulation material A  
E : Outer covering B  
A : High press. pipe  
C : Electric wire  
E : Insulator  
B : Low press. pipe  
D : Finishing tape  
[Fig. 9.4.4]  
<A> Inner wall (concealed)  
<B> Outer wall  
<C> Outer wall (exposed) <D> Floor (waterproofing)  
<E> Roof pipe shaft  
<F> Penetrating portion on fire  
limit and boundary wall  
I
D
J
D
G
D
B
E
C
F
B
A B  
A
B
H
F
I
G
B
A
1m  
1m  
[3.28 ft]  
[3.28 ft]  
A : Sleeve  
B : Heat insulating material  
D : Caulking material  
F : Waterproofing laye  
H : Lagging material  
C : Lagging  
E : Band  
G : Sleeve with edge  
I : Mortar or other incombustible caulking  
J : Incombustible heat insulation material  
10.2  
10  
[Fig. 10.2.1]  
A : Power source  
B : Transmission line  
C : Ground screw  
L1 L2 L3  
TB1  
M1M2 M1M2 S  
TB3  
TB7  
A
B
C
4
 
10.3  
L1  
[Fig. 10.3.1]  
A
C
OC  
<A> Change the jumper connector  
from CN41 to CN40  
IC  
IC  
IC  
IC  
CN40  
BC  
BS  
(51)  
(52)  
M1M2S  
(01)  
TB5  
M1M2S  
(02)  
TB5  
M1M2S  
(55)  
M1M2S  
(05)  
TB5  
M1M2S  
(06)  
TB5  
M1M2S  
<B> SW2-1:ON  
TB3  
M1M2  
M1M2S  
TB7  
r3  
D
A
B
A
B
A
B
(101)  
(105)  
(155)  
<C> Keep the jumper connector on  
CN41  
RC E  
RC  
RC  
OC  
<B> SW2-1:ON  
L3  
L4  
IC  
(03)  
IC  
(04)  
IC  
(07)  
CN40  
BC  
(53)  
(54)  
TB3  
M1M2S  
TB5  
M1M2S  
TB5  
M1M2S  
TB5  
M1M2S  
M1M2  
M1M2S  
TB7  
System  
controller  
M1M2S  
A
B
(104)  
[Fig. 10.3.2]  
RC  
B
L1  
<A> Change the jumper connector  
from CN41 to CN40  
A
C
OC  
IC  
(01)  
IC  
(02)  
IC  
(05)  
IC  
(06)  
CN40  
<B> SW2-1:ON  
BC  
BS  
(51)  
c2  
c2  
(52)  
(55)  
M1M2S  
M1M2S  
TB3  
TB5  
M1M2S  
TB15  
TB5  
M1M2S  
TB15  
TB5  
M1M2S  
TB15  
TB5  
M1M2S  
TB15  
M1M2  
1
2
1
2
1
2
1
2
M1M2S  
TB7  
c4  
<C> Keep the jumper connector on  
CN41  
D
A
B
A
B
A
B
<B> SW2-1:ON  
MA  
MA E  
MA  
OC  
L3  
L4  
A : Group 1  
IC  
(03)  
IC  
(04)  
IC  
(07)  
CN40  
BC  
(53)  
B : Group 4  
(54)  
TB3  
M1M2S  
TB5  
M1M2S  
TB15  
TB5  
M1M2S  
TB15  
TB5  
M1M2S  
TB15  
C : Group 5  
M1M2  
1
2
1
2
1
2
M1M2S  
TB7  
D : Shielded wire  
E : Sub remote  
System  
controller  
M1M2S  
controller  
( ): Address  
A
B
MA  
B
10.4  
[Fig. 10.4.1]  
F
A
~208 - 230 V  
B
A : Switch (breakers for wiring and cur-  
rent leakage)  
'
C
C
B : Heat source unit  
C : BC controller (main)  
D
'
: BC controller (sub)  
C
F
A
~208 - 230 V  
D : Pull box  
E : Indoor unit  
E
E
E
E
F : Breakers for current leakage  
5
 
Contents  
1. Safety precautions ...................................................................................... 6  
1.1. Before installation and electric work .......................................... 6  
1.2. Precautions for devices that use R410A refrigerant .................. 6  
1.3. Before getting installed .............................................................. 7  
1.4. Before installation electrical work .............................................. 7  
1.5. Before starting the test run ........................................................ 7  
2. About the product ....................................................................................... 7  
3. Specifications .............................................................................................. 7  
4. Confirmation of parts attached ................................................................... 8  
5. Lifting method ............................................................................................. 8  
6. Installation of unit and service space .......................................................... 8  
6.1. Installation ................................................................................. 8  
6.2. Service space ............................................................................ 8  
7. Water pipe installation................................................................................. 8  
7.1. Precautions during installation .................................................. 8  
7.2. Insulation installation ................................................................. 8  
7.3. Water processing and water quality control............................... 8  
7.4. Pump interlock........................................................................... 9  
8. Refrigerant piping installation ..................................................................... 9  
8.1. Caution ...................................................................................... 9  
8.2. Refrigerant piping system.......................................................... 9  
9. Additional refrigerant charge ..................................................................... 10  
9.1. Calculation of additional refrigerant charge ............................. 10  
9.2. Precautions concerning piping connection and  
valve operation ........................................................................ 10  
9.3. Airtight test, evacuation, and refrigerant charging ................... 11  
9.4. Thermal insulation of refrigerant piping ................................... 12  
10. Wiring ........................................................................................................ 12  
10.1. Caution .................................................................................... 12  
10.2. Control box and connecting position of wiring ......................... 12  
10.3. Wiring transmission cables...................................................... 12  
10.4. Wiring of main power supply and equipment capacity ............ 14  
11. Test run ..................................................................................................... 14  
11.1. The following phenomena do not represent trouble  
(emergency) ............................................................................ 14  
12. Information on rating plate ........................................................................ 14  
1. Safety precautions  
Securely install the heat source unit terminal cover (panel).  
- If the terminal cover (panel) is not installed properly, dust or water may enter  
the heat source unit and fire or electric shock may result.  
When installing and moving the air conditioner to another site, do not  
charge it with a refrigerant different from the refrigerant (R410A) speci-  
fied on the unit.  
1.1. Before installation and electric work  
s Before installing the unit, make sure you read all the “Safety  
precautions”.  
s The “Safety precautions” provide very important points re-  
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-  
erant cycle may malfunction and the unit may be damaged.  
If the air conditioner is installed in a small room, measures must be taken  
to prevent the refrigerant concentration from exceeding the safety limit  
even if the refrigerant should leak.  
- Consult the dealer regarding the appropriate measures to prevent the safety  
limit from being exceeded. Should the refrigerant leak and cause the safety  
limit to be exceeded, hazards due to lack of oxygen in the room could result.  
When moving and reinstalling the air conditioner, consult the dealer or  
an authorized technician.  
- If the air conditioner is installed improperly, water leakage, electric shock, or  
fire may result.  
After completing installation work, make sure that refrigerant gas is not  
leaking.  
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or  
other heat source, it may generate noxious gases.  
Do not reconstruct or change the settings of the protection devices.  
- If the pressure switch, thermal switch, or other protection device is shorted  
and operated forcibly, or parts other than those specified by Mitsubishi Elec-  
tric are used, fire or explosion may result.  
garding safety. Make sure you follow them.  
Symbols used in the text  
Warning:  
Describes precautions that should be observed to prevent danger of injury  
or death to the user.  
Caution:  
Describes precautions that should be observed to prevent damage to the  
unit.  
Symbols used in the illustrations  
: Indicates an action that must be avoided.  
: Indicates that important instructions must be followed.  
: Indicates a part which must be grounded.  
: Beware of electric shock. (This symbol is displayed on the main unit label.)  
<Color: yellow>  
To dispose of this product, consult your dealer.  
The installer and system specialist shall secure safety against leakage  
according to local regulation or standards.  
- Following standards may be applicable if local regulation are not available.  
Pay a special attention to the place, such as a basement, etc. where re-  
frigeration gas can stay, since refrigeration is heavier than the air.  
Warning:  
Carefully read the labels affixed to the main unit.  
Warning:  
Ask the dealer or an authorized technician to install the air conditioner.  
- Improper installation by the user may result in water leakage, electric shock,  
or fire.  
1.2. Precautions for devices that use R410A  
refrigerant  
Install the unit in a place that can withstand its weight.  
- Inadequate strength may cause the unit to fall down, resulting in injuries.  
Use the specified cables for wiring. Make the connections securely so  
that the outside force of the cable is not applied to the terminals.  
- Inadequate connection and fastening may generate heat and cause a fire.  
Prepare for rain and other moisture and earthquakes and install the unit  
at the specified place.  
- Improper installation may cause the unit to topple over and result in injury.  
Always use an filter and other accessories specified by Mitsubishi Electric.  
- Ask an authorized technician to install the accessories. Improper installation  
by the user may result in water leakage, electric shock, or fire.  
Never repair the unit. If the air conditioner must be repaired, consult the  
dealer.  
- If the unit is repaired improperly, water leakage, electric shock, or fire may  
result.  
If refrigerant gas leaks during installation work, ventilate the room.  
- If the refrigerant gas comes into contact with a flame, poisonous gases will  
be released.  
Install the air conditioner according to this Installation Manual.  
- If the unit is installed improperly, water leakage, electric shock, or fire may  
result.  
Have all electric work done by a licensed electrician according to “Elec-  
tric Facility Engineering Standard” and “Interior Wire Regulations”and  
the instructions given in this manual and always use a special circuit.  
- If the power source capacity is inadequate or electric work is performed im-  
properly, electric shock and fire may result.  
Caution:  
Do not use the existing refrigerant piping.  
- The old refrigerant and refrigerator oil in the existing piping contains a large  
amount of chlorine which may cause the refrigerator oil of the new unit to  
deteriorate.  
- R410A is a high-pressure refrigerant and can cause the existing piping to  
burst.  
Use refrigerant piping made of phosphorus deoxidized copper and copper  
alloy seamless pipes and tubes. In addition, be sure that the inner and  
outer surfaces of the pipes are clean and free of hazardous sulphur, ox-  
ides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.  
- Contaminants on the inside of the refrigerant piping may cause the refriger-  
ant residual oil to deteriorate.  
Store the piping to be used during installation indoors and keep both  
ends of the piping sealed until just before brazing. (Store elbows and  
other joints in a plastic bag.)  
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and  
compressor trouble may result.  
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator  
oil to coat flares and flange connections.  
- The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.  
Use liquid refrigerant to fill the system.  
- If gas refrigerant is used to seal the system, the composition of the refriger-  
ant in the cylinder will change and performance may drop.  
6
 
Do not use a refrigerant other than R410A.  
- The some electric parts should be damaged when power is supplied under  
the miss wiring.  
Install the power cable so that tension is not applied to the cable.  
- Tension may cause the cable to break and generate heat and cause a fire.  
Install a leak circuit breaker, as required.  
- If a leak circuit breaker is not installed, electric shock may result.  
Use power line cables of sufficient current carrying capacity and rating.  
- Cables that are too small may leak, generate heat, and cause a fire.  
Use only a circuit breaker and fuse of the specified capacity.  
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may  
result in a general unit failure or fire.  
- If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the  
refrigerant may cause the refrigerator oil to deteriorate.  
Use a vacuum pump with a reverse flow check valve.  
- The vacuum pump oil may flow back into the refrigerant cycle and cause the  
refrigerator oil to deteriorate.  
Do not use the following tools that are used with conventional refrigerants.  
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,  
refrigerant charge base, refrigerant recovery equipment)  
- If the conventional refrigerant and refrigerator oil are mixed in the R410A,  
the refrigerant may deteriorated.  
- If water is mixed in the R410A, the refrigerator oil may deteriorate.  
- Since R410A does not contain any chlorine, gas leak detectors for conven-  
tional refrigerants will not react to it.  
Do not use a charging cylinder.  
- Using a charging cylinder may cause the refrigerant to deteriorate.  
Be especially careful when managing the tools.  
Do not wash the air conditioner units.  
- Washing them may cause an electric shock.  
Be careful that the installation base is not damaged by long use.  
- If the damage is left uncorrected, the unit may fall and cause personal injury  
or property damage.  
Install the drain piping according to this Installation Manual to ensure  
proper drainage. Wrap thermal insulation around the pipes to prevent  
condensation.  
- Improper drain piping may cause water leakage and damage to furniture  
and other possessions.  
Be very careful about product transportation.  
- Only one person should not carry the product if it weighs more than 20 kg  
[45 LBS].  
- Some products use PP bands for packaging. Do not use any PP bands for a  
means of transportation. It is dangerous.  
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.  
1.3. Before getting installed  
Caution:  
Do not install the unit where combustible gas may leak.  
- If the gas leaks and accumulates around the unit, an explosion may result.  
Do not use the air conditioner where food, pets, plants, precision instru-  
ments, or artwork are kept.  
- The quality of the food, etc. may deteriorate.  
- When transporting the heat source unit, support it at the specified positions  
on the unit base. Also support the heat source unit at four points so that it  
cannot slip side ways.  
Do not use the air conditioner in special environments.  
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of  
the air conditioner or damage its parts.  
Safely dispose of the packing materials.  
When installing the unit in a hospital, communication station, or similar  
place, provide sufficient protection against noise.  
- Packing materials, such as nails and other metal or wooden parts, may cause  
stabs or other injuries.  
- The inverter equipment, private power generator, high-frequency medical  
equipment, or radio communication equipment may cause the air conditioner  
to operate erroneously, or fail to operate. On the other hand, the air condi-  
tioner may affect such equipment by creating noise that disturbs medical  
treatment or image broadcasting.  
Do not install the unit on a structure that may cause leakage.  
- When the room humidity exceeds 80 % or when the drain pipe is clogged,  
condensation may drip from the indoor unit.Perform collective drainage work  
together with the heat source unit, as required.  
- Tear apart and throw away plastic packaging bags so that children will not  
play with them. If children play with a plastic bag which was not torn apart,  
they face the risk of suffocation.  
1.5. Before starting the test run  
Caution:  
Turn on the power at least 12 hours before starting operation.  
- Starting operation immediately after turning on the main power switch can  
result in severe damage to internal parts. Keep the power switch turned on  
during the operational season.  
1.4. Before installation electrical work  
Do not touch the switches with wet fingers.  
Warning  
- Touching a switch with wet fingers can cause electric shock.  
Do not touch the refrigerant pipes during and immediately after operation.  
- During and immediately after operation, the refrigerant pipes are may be hot  
and may be cold, depending on the condition of the refrigerant flowing through  
the refrigerant piping, compressor, and other refrigerant cycle parts. Your  
hands may suffer burns or frostbite if you touch the refrigerant pipes.  
Do not operate the air conditioner with the panels and guards removed.  
- Rotating, hot, or high-voltage parts can cause injuries.  
Do not turn off the power immediately after stopping operation.  
- Always wait at least five minutes before turning off the power. Otherwise,  
water leakage and trouble may occur.  
Do not touch the surface of the compressor during servicing.  
- If unit is connected to the supply and not running, crank case heater at  
compressor is operating.  
When installing or relocating the unit, make sure that no substance other  
than the specified refrigerant (R410A) enters the refrigerant circuit.  
Any presence of foreign substance such as air can cause abnormal pres-  
sure rise or explosion.  
Caution:  
Ground the unit.  
- Do not connect the ground wire to gas or water pipes, lightning rods, or  
telephone ground lines. Improper grounding may result in electric shock.  
The reverse phase of L lines (L1, L2, L3) can be detected (Error cord: 4103),  
but the reverse phase of L lines and N line can be not be detected.  
2. About the product  
This unit uses R410A-type refrigerant  
Do not use the existing piping, as it contains chlorine, which is found in con-  
ventional refrigerating machine oil and refrigerant.This chlorine will deteriorate  
the refrigerant machine oil in the new equipment.The existing piping must not  
be used as the design pressure in systems using R410A is higher than that in  
the systems using other types of refrigerant and the existing pipes may burst.  
Piping for systems using R410A may be different from that for systems using  
conventional refrigerant because the design pressure in systems using R410A  
is higher. Refer to Data Book for more information.  
Some of the tools and equipment used for installation with systems that use  
other types of refrigerant cannot be used with the systems using R410A. Refer  
to Data Book for more information.  
3. Specifications  
Model  
PQRY-P72TGMU-A  
46 dB <A>  
257 kg [568 LBS]  
PQRY-P96TGMU-A  
47 dB <A>  
260 kg [574 LBS]  
Noise level  
Net weight  
Allowable pressure  
Refrigerant  
HP: 4.15 MPa [601 psi], LP: 2.21 MPa [320 psi]  
R410A: 7.5 kg [16 LBS 9 oz] R410A: 8.5 kg [18 LBS 12 oz]  
Total capacity  
Model / Quantity  
50 ~ 150 %  
Indoor units  
P06 ~ P96 / 1 ~ 15  
P06 ~ P96 / 1 ~ 19  
Operation temperature  
Maximum water pressure  
Rated water volume  
Water temperature: 10˚C ~ 45˚C [50˚F ~ 113˚F] Note.1  
1.0 MPa [145 psi]  
4.56 m3/h [1204 G/h]  
3.9 ~ 6.8 m3/h [1030 ~ 1795 G/h]  
5.76 m3/h [1521 G/h]  
Allowable water volume  
4.5 ~ 7.2 m3/h [1188 ~ 1901 G/h]  
Note 1. When the total capacity of indoor units exceeds 130% of heat source units capacity, the operating temperature range of circulating water is 15˚C ~ 45˚C [59˚F ~ 113˚F]  
7
 
4. Confirmation of parts attached  
1
3
Connecting pipe × 1 (Connecting pipe is fixed with the unit.)  
Bushing × 2  
2
Packing (inside ø23 [29/32 in], outside ø35 [1-13/32 in]) × 1  
5. Lifting method  
[Fig. 5.0.1] (P.2)  
Caution:  
Be very careful when carrying the product.  
- Do not have only one person to carry product if it is more than 20 kg [46 LBS].  
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.  
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.  
- When carrying the heat source unit, be sure to support it at four points. Carrying with 3-point support may make the heat source unit unstable, resulting in it falling.  
6. Installation of unit and service space  
Warning:  
6.1. Installation  
Be sure to install unit in a place strong enough to withstand its weight.  
Any lack of strength may cause unit to fall down, resulting in a personal  
injury.  
Using the anchoring holes shown below, firmly bolt the unit to the base.  
[Fig. 6.1.1] (P.2)  
Have installation work in order to protect against earthquake.  
Any installation deficiency may cause unit to fall down, resulting in a  
personal injury.  
A
C
Heat source unit  
(Top view)  
B
4-ø14 [9/16] (Anchoring hole)  
Bases and anti-vibration  
Be sure to install unit in a place strong enough to withstand its weight. If the  
base is unstable, reinforce with a concrete base.  
6.2. Service space  
Please allow for the following service spaces after installation.  
(All servicing can be performed from the front of the unit)  
The unit must be anchored on a level surface. Use a level to check after  
installation.  
[Fig. 6.2.1] (P.2)  
Anti-vibration pads must be placed under the base of the unit.  
A
C
Piping space (for side piping)  
Service space (front side)  
B
D
Heat source unit  
(Top view)  
If the unit is installed near a room where noise is a problem, using an anti-  
vibration stand on the base of the unit is recommended.  
[Fig. 6.1.2] (P.2)  
[Fig. 6.2.2] (P.2)  
D
Anti-vibration pad etc.  
E
Concrete base  
E
G
Piping space (for top piping)  
Heat source unit  
F
H
Piping space (for side piping)  
(Front view)  
7. Water pipe installation  
City Multi WR2 Series pipes are similar to other air-conditioning pipes, how-  
ever, please observe the following precautions during installation.  
[Fig. 7.1.1] (P.2)  
A
C
E
G
Water circulation pipe  
B
D
F
H
Close valve  
Water outlet  
Y-type strainer  
Drain pipe  
Close valve  
7.1. Precautions during installation  
Refrigerant piping  
Water inlet  
Use the reverse-return method to insure proper pipe resistance to each unit.  
To insure easy maintenance, inspection, and replacement of the unit, use a  
proper joint, valve, etc. on the water intake and outlet port. In addition, be sure  
to install a strainer on the water intake pipe. (In order to maintain the heat  
source unit, a strainer on the circulating water inlet is necessary.)  
* An example of the heat source unit installation is shown in the diagram be-  
low.  
7.2. Insulation installation  
With City Multi WR2 Series piping, as long as the temperature range of the circu-  
lating water is kept to average temperatures year-round (30 °C [86 °F] in the sum-  
mer, 20 °C [68 °F] in the winter), there is no need to insulate or otherwise protect  
indoor piping from exposure.You should use insulation in the following situations:  
Install a suitable air vent on the water pipe. After sending water through the  
pipe, be sure to vent the excess air.  
Any heat source piping.  
Indoor piping in cold-weather regions where frozen pipes are a problem.  
When air coming from the outside causes condensation to form on piping.  
Any drainage piping.  
Compressed water may form in the low-temperature sections of heat source  
unit. Use a drainage pipe connected to the drain valve at the base of the unit to  
drain the water.  
There is a water vent plug in the center of the heat exchanger water inlet head  
at the middle of the unit. Use this for maintenance, etc.  
In addition, do not allow any of the unit’s electrical parts (such as the solenoid  
valve coil or compressor power supply) to become wet.  
7.3. Water processing and water quality con-  
trol  
To preserve water quality, use the closed type of cooling tower for WR2. When the  
circulating water quality is poor, the water heat exchanger can develop scales,  
leading to a reduction in heat-exchange power and possible corrosion of the heat  
exchanger.Please pay careful attention to water processing and water quality control  
when installing the water circulation system.  
Install a back flow-prevention valve on the pump and a flexible joint to prevent  
excess vibration.  
Use a sleeve to protect the pipes where they go through a wall.  
Use metal fittings to secure the pipes, and install them so that they have maxi-  
mum protection against breakage and bending.  
Removal of foreign objects or impurities within the pipes.  
During installation, be careful that foreign objects, such as welding fragments,  
sealant particles, or rust, do not enter the pipes.  
Do not confuse the water intake and outlet valves.  
This unit doesn’t have any heater to prevent freezing within tubes. When the  
water flow is stopped on low ambient, take out the water from tubes.  
Water Quality Processing  
1
Depending on the quality of the cold-temperature water used in the air-  
conditioner, the copper piping of the heat exchanger may become corroded.  
We recommend regular water quality processing.  
The unused knockout holes should be closed and the opening of refrigerant  
pipes, water pipes, power source and transmission wires should be filled with  
putty and so on to prevent from rain. (field construction)  
Cold water circulation systems using open heat storage tanks are  
particularly prone to corrosion.  
Example of heat source unit installation (using left piping)  
When using an open-type heat storage tank, install a water-to-water heat  
exchanger, and use a closed-loop circuit on the air conditioner side. If a  
water supply tank is installed, keep contact with air to a minimum, and  
keep the level of dissolved oxygen in the water no higher than 1mg/r.  
8
 
2
Water quality standard  
3
4
Please consult with a water quality control specialist about water quality  
control methods and water quality calculations before using anti-corrosive  
solutions for water quality management.  
Lower mid-range  
Tendency  
Scale-  
temperature water system  
Recirculating  
When replacing a previously installed air conditioning device (even when  
only the heat exchanger is being replaced), first conduct a water quality  
analysis and check for possible corrosion.  
Corrosion can occur in cold-water systems even if there has been no prior  
signs of corrosion.  
Items  
Make-up  
water  
water  
Corrosive  
[20<T<60°C]  
forming  
[68<T<140°F]  
7.0 ~ 8.0  
30 or less  
[300 or less]  
50 or less  
50 or less  
pH (25°C) [77°F]  
Electric conductivity (mS/m) (25°C) [77°F] 30 or less  
(µ s/cm) (25°C) [77°F] [300 or less]  
7.0 ~ 8.0  
If the water quality level has dropped, please adjust water quality suffi-  
ciently before replacing the unit.  
Chloride ion  
(mg Cl-/r) 50 or less  
(mg SO42-/r) 50 or less  
Sulfate ion  
7.4. Pump interlock  
The heat source unit may become damaged if it is operated with no water circulat-  
ing through the pipes.  
Standard  
Acid consumption (pH4.8)  
(mg CaCO3/r)  
items  
50 or less  
50 or less  
70 or less  
50 or less  
30 or less  
0.3 or less  
0.1 or less  
not to be  
detected  
0.1 or less  
0.3 or less  
4.0 or less  
Total hardness  
(mg CaCO3/r) 70 or less  
Be sure to interlock unit operation and the water-circuit pump. Use the terminal  
blocks for interlocking (TB8-3, 4) that can be found on the unit.  
In the case of a pump interlock circuit signal connection to the TB8-3, 4, remove  
the short-circuit wire. Also, to prevent mistaken error detection, resulting from a  
poor connection, in the pressure valve 63PW, use a low maintained current of 5mA  
or less.  
Calcium hardness (mg CaCO3/r) 50 or less  
Ionic silica  
Iron  
(mg SiO2/r) 30 or less  
(mg Fe/r) 1.0 or less  
(mg Cu/r) 1.0 or less  
Refer-  
ence  
Copper  
items  
not to be  
(mg S2-/r)  
Sulfide ion  
[Fig. 7.4.1] (P.2)  
detected  
(mg NH4+/r) 0.3 or less  
(mg Cl/r) 0.25 or less  
A
B
Short-circuit wire (Connected before delivery from manufacturer)  
Pump interlock circuit connection  
Ammonium ion  
Residual chlorine  
Free carbon dioxide (mg CO2/r) 0.4 or less  
Ryzner stability index  
Reference : Guideline of Water Quality for Refrigeration and Air Conditioning  
Equipment. (JRA GL02E-1994)  
8. Refrigerant piping installation  
City Multi WR2 Series is constituted by an end branching system in which the  
refrigerant piping from heat source unit is branched at BC controller and connected  
to each indoor unit.  
The connection method adapted is brazing connection for high pressure pipe and  
low pressure pipe between heat source unit and BC controller, and flare connec-  
tion between BC controller and indoor unit. Brazing connection is employed for  
joint pipe set and branch pipe set.  
A
B
Residues in commercially available antioxidants may have adverse effects on  
the equipment. Braze only with non-oxide brazing material. The use of other  
brazing material may result in compressor damage.  
(Refer to item 9.2. for detailed information on pipe connections and valve op-  
erations.)  
Never perform heat source unit piping connection work when it is rain-  
ing.  
Warning:  
Warning  
Always use extreme care to prevent the refrigerant gas from leaking while  
using fire or flame. If the refrigerant gas comes in contact with a flame from  
any source, such as a gas stove, it breaks down and generates a poisonous  
gas which can cause gas poisoning. Never weld in an unventilated room.  
Always conduct an inspection for gas leakage after installation of the refrig-  
erant piping has been completed.  
When installing and moving the unit, do not charge it with refrigerant other  
than the refrigerant specified on the unit.  
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-  
function and result in severe damage.  
Caution:  
Use a vacuum pump with a reverse flow check valve.  
- If the vacuum pump does not have a reverse flow check valve, the vacuum  
pump oil may flow back into the refrigerant cycle and cause deterioration of  
the refrigerator oil and other trouble.  
Do not use the tools shown below used with conventional refrigerant.  
(Gauge manifold, charge hose, gas leak detector, check valve, refrigerant  
charge base, vacuum gauge, refrigerant recovery equipment)  
- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-  
erator oil to deteriorate.  
8.1. Caution  
This unit uses refrigerant R410A. Follow the local regulations on materials and  
pipe thickness when selecting pipes.  
1
Use the following materials for refrigeration piping.  
Material: Use refrigerant piping made of phosphorus deoxidized copper.  
In addition, be sure that the inner and outer surfaces of the pipes are clean  
and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils,  
moisture, or any other contaminant.  
- Mixing of water will cause the refrigerator oil to deteriorate.  
- R410A refrigerant does not contain any chlorine.Therefore, gas leak detec-  
tors for conventional refrigerants will not react to it.  
Manage the tools more carefully than normal.  
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-  
riorate.  
2
3
4
5
Commercially available piping often contains dust and other materials. Always  
blow it clean with a dry inert gas.  
Use care to prevent dust, water or other contaminants from entering the piping  
during installation.  
Reduce the number of bending portions as much as possible, and make bend-  
ing radius as big as possible.  
Never use existing refrigerant piping.  
- The large amount of chlorine in conventional refrigerant and refrigerator oil  
in the existing piping will cause the new refrigerant to deteriorate.  
Store the piping to be used during installation indoors and keep both  
ends of the piping sealed until just before brazing.  
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and  
the compressor may fail.  
Do not use a charging cylinder.  
- Using a charging cylinder may cause the refrigerant to deteriorate.  
Do not use special detergents for washing piping.  
Always observe the restrictions on the refrigerant piping (such as rated length,  
the difference between high/low pressures, and piping diameter). Failure to do  
so can result in equipment failure or a decline in heating/cooling performance.  
6
Either a lack or an excess of refrigerant causes the unit to make an emergency  
stop. Charge the system with an appropriate amount of refrigerant. At such a  
time, always properly charge the unit. When servicing, always check the notes  
concerning pipe length and amount of additional refrigerant at both locations,  
the refrigerant volume calculation table on the back of the service panel and  
the additional refrigerant section on the labels for the combined number of  
indoor units.  
8.2. Refrigerant piping system  
Connection Example  
7
8
Use liquid refrigerant to fill the system.  
Never use refrigerant to perform an air purge. Always evacuate using a vacuum  
pump.  
[Fig. 8.2.1] (P.3)  
Å
Ç
Ì
¬
A
C
E
Heat source model  
Low press. side  
ı
Î
Ï
Ó
Ô
B
D
High press. side  
9
0
Always insulate the piping properly. Insufficient insulation will result in a de-  
cline in heating/cooling performance, water drops from condensation and other  
such problems.  
Total capacity of indoor units  
Gas line  
Liquid line  
High press. gas pipe  
Liquid pipe  
Low press. gas pipe  
Model number  
When connecting the refrigerant piping, make sure the ball valve of the heat  
source unit is completely closed (the factory setting) and do not operate it until  
the refrigerant piping for the heat source and indoor units has been connected,  
a refrigerant leakage test has been performed and the evacuation process has  
been completed.  
BC controller (standard)  
BC controller (sub)  
Indoor unit (72, 96)  
BC controller (main)  
Indoor unit (06 ~ 54)  
9
 
9. Additional refrigerant charge  
At the time of shipping, the heat source unit is charged with the refrigerant. As this  
charge does not include the amount needed for extended piping, additional charg-  
ing for each refrigerant line will be required on site. In order that future servicing  
may be properly provided, always keep a record of the size and length of each  
refrigerant line and the amount of additional charge by writing it in the space pro-  
vided on the heat source unit.  
9.2. Precautions concerning piping connec-  
tion and valve operation  
Conduct piping connection and valve operation accurately.  
Flange type side connecting pipe is assembled in factory before shipment.  
1
For brazing to the connecting pipe with flange, remove the connecting pipe  
with flange from the ball valve, and braze it outside of the unit.  
9.1. Calculation of additional refrigerant  
charge  
2
During the time when removing the connecting pipe with flange, remove  
the seal attached on the rear side of this sheet and paste it onto the flange  
surface of the ball valve to prevent the entry of dust into the valve.  
Calculate the amount of additional charge based on the length of the piping  
extension and the size of the refrigerant line.  
3
4
The refrigerant circuit is closed with a round, close-packed packing upon  
shipment to prevent gas leak between flanges. As no operation can be  
done under this state, be sure to replace the packing with the hollow pack-  
ing attached at the piping connection.  
Use the table to the below as a guide to calculating the amount of additional  
charging and charge the system accordingly.  
If the calculation results in a fraction of less than 0.1 kg [4 oz], round up to the  
next 0.1 kg [4 oz]. For example, if the result of the calculation was 10.62 kg  
[373.3 oz], round the result up to 10.7 kg [376 oz].  
At the mounting of the hollow packing, wipe off dust attached on the flange  
sheet surface and the packing. Coat refrigerating machine oil (Ester oil,  
ether oil or alkylbenzene [small amount]) onto both surfaces of the pack-  
ing.  
<Additional Charge>  
High pressure  
pipe size  
Total length of  
ø19.05 [3/4]  
Additional  
refrigerant  
charge  
High pressure  
pipe size  
Total length of  
ø15.88 [5/8]  
High pressure  
pipe size  
Total length of  
ø12.7 [1/2]  
High pressure  
pipe size  
Total length of  
ø9.52 [3/8]  
[Fig. 9.2.1] (P.3)  
A
B
Close-packed packing  
Hollow packing  
=
+
+
+
+
(m) × 0.16 (kg/m)  
(in) × 1.72(oz/ft)  
(kg) [oz]  
(m) × 0.11 (kg/m)  
(in) × 1.18 (oz/ft)  
(m) × 0.12 (kg/m)  
(in) × 1.29 (oz/ft)  
(m) × 0.06 (kg/m)  
(in) × 0.65 (oz/ft)  
After evacuation and refrigerant charge, ensure that the handle is fully open. If  
operating with the valve closed, abnormal pressure will be imparted to the  
high- or low-pressure side of the refrigerant circuit, giving damage to the com-  
pressor, four-way valve, etc.  
High pressure  
pipe size  
Total length of  
ø6.35 [1/4]  
+ α1 + α2  
Determine the amount of additional refrigerant charge by using the formula,  
and charge refrigerant additionally through the service port after completing  
piping connection work.  
(m) × 0.024 (kg/m)  
(in) × 0.26 (oz/ft)  
After completing work, tighten the service port and cap securely not to gener-  
ate gas leak.  
<Example 1>  
Indoor No. 1: 15 A: ø19.05 [3/4] 40 m [131 ft] a: ø6.35 [1/4] 10 m [32 ft]  
No. 2: 72 B: ø9.52 [3/8] 10 m [32 ft] b: ø9.52 [3/8] 5 m [16 ft]  
Flare machining dimension for systems using R410A is larger than that for  
systems using other types of refrigerant in order to increase the air tightness.  
At the  
conditions  
below:  
No. 3: 15  
No. 4: 12  
No. 5: 24  
c: ø6.35 [1/4] 10 m [32 ft]  
d: ø6.35 [1/4] 10 m [32 ft]  
e: ø9.52 [3/8] 10 m [32 ft]  
Refer to the table on the below for flare machining dimensions, and follow the  
regulations set forth by the local authorities. Seal off the opening of the pipe  
with a closure material (not supplied) to keep small animals from entering the  
pipe if that is a concern.  
The total length of each liquid line is as follows:  
ø19.05 [3/4]: A = 40 m [131ft]  
flare machining dimension (mm)  
outer diameter  
ø9.52 [3/8]: B + b + e = 10 [32] + 5 [16] + 10 [32] = 25 m [80 ft]  
ø6.35 [1/4]: a + c + d = 10 [32] + 10 [32] + 10 [32] = 30 m [96 ft]  
dimension A  
R410A  
9.1  
size in inches  
Therefore,  
<Calculation example>  
Additional refrigerant charge  
= 40 [131] × 0.16 [1.72] + 25 [80] × 0.06 [0.65]  
+ 30 [96] × 0.024 [0.26] + 2.0 [71oz] = 10.7 kg [376oz]  
ø6.35  
ø9.52  
1/4"  
3/8"  
1/2"  
5/8"  
3/4"  
13.2  
ø12.70  
ø15.88  
ø19.05  
16.6  
19.7  
24.0  
<Example 2>  
Indoor No. 1: 08 A: ø19.05 [3/4] 40 m [131 ft] a: ø6.35 [1/4] 10 m [32 ft]  
No. 2: 06 B: ø9.52 [3/8] 10 m [32 ft] b: ø6.35 [1/4] 5 m [16 ft]  
No. 3: 12 C: ø12.7 [1/2] 10 m [32 ft] c: ø6.35 [1/4] 10 m [32 ft]  
No. 4: 12 D: ø9.52 [3/8] 10 m [32 ft] d: ø6.35 [1/4] 10 m [32 ft]  
flare nut size (mm)  
dimension B  
R410A  
17.0  
At the  
conditions  
below:  
outer diameter  
size in inches  
ø6.35  
ø9.52  
1/4"  
3/8"  
1/2"  
5/8"  
3/4"  
No. 5: 12  
No. 6: 72  
No. 7: 06  
e: ø6.35 [1/4] 10 m [32 ft]  
f: ø9.52 [3/8] 10 m [32 ft]  
g: ø6.35 [1/4] 5 m [16 ft]  
22.0  
ø12.70  
ø15.88  
ø19.05  
26.0  
B
29.0  
The total length of each liquid line is as follows:  
ø19.05 [3/4]: A = 40 m [131 ft]  
36.0  
ø12.7 [1/2]: C = 10 m [32 ft]  
[Fig. 9.2.2] (P.3)  
ø9.52 [3/8]: B + D + f = 10 [32] + 10 [32] + 10 [32] = 30 m [96 ft]  
ø6.35 [1/4]: a + b + c + d + e + g = 10 [32] + 5 [16] + 10 [32] + 10 [32] + 10 [32] +  
5 [16] = 50 m [160 ft]  
<A> [Ball valve (Low press. side/flanged type)]  
<B> [Ball valve (High press. side/flared type)]  
<C> This figure shows the valve in the fully open state.  
Therefore,  
A
Valve stem  
<Calculation example>  
Additional refrigerant charge  
= 40 [131] × 0.16 [1.72] + 10 [32] × 0.12 [1.29] + 30 [96] × 0.06 [0.65] +  
50 [160] × 0.024 [0.26] + 2.5 [89] + 2.0 [71] = 15.1 kg [531 oz]  
[Fully closed at the factory, when connecting the piping, when evacuating, and  
when charging additional refrigerant. Open fully after the operations above are  
completed.]  
B
C
Stopper pin [Prevents the valve stem from turning 90° or more.]  
Packing (Accessory)  
[Manufacturer: Nichiasu corporation]  
[Type: T/#1991-NF]  
Value of α1  
Total capacity of connecting indoor units  
to Model 30  
α 1  
1.0 kg [36 oz]  
1.5 kg [53 oz]  
2.0 kg [71 oz]  
2.5 kg [89 oz]  
D
Connecting pipe (Accessory)  
[Use packing and securely install this pipe to the valve flange so that gas leakage  
will not occur. (Tightening torque:40 N·m [400 kg·cm]) Coat both surfaces of the  
packing with refrigerating machine oil. (Ester oil, ether oil or alkylbenzene [small  
amount])]  
Models 31 to 60  
Models 61 to 126  
Models 127 to 180  
E
F
Open (Operate slowly)  
Value of α2  
Cap, copper packing  
[Remove the cap and operate the valve stem. Always reinstall the cap after opera-  
tion is completed.(Valve stem cap tightening torque:23 ~ 27 N·m [230 ~ 270 kg·cm])]  
α 2  
0 kg [0 oz]  
BC controller (standard, main only)  
BC controller (sub) connected (one)  
BC controller (sub) connected (two)  
1.0 kg [36 oz]  
2.0 kg [71 oz]  
10  
 
G
H
Service port  
Caution:  
[Use this port to evacuate the refrigerant piping and add an additional charge at  
the site.  
Open and close the port using a double-ended wrench.  
Always reinstall the cap after operation is completed. (Service port cap tightening  
torque: 12 ~ 15 N·m [120 ~ 150 kg·cm])  
Always remove the connecting pipe from the ball valve and braze it out-  
side the unit.  
- Brazing the connecting pipe while it is installed will heat the ball valve and  
cause trouble or gas leakage. The piping, etc. inside the unit may also be  
burned.  
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerat-  
ing machine oil to coat flares and flange connections.  
- The refrigerating machine oil will degrade if it is mixed with a large amount of  
mineral oil.  
Flare nut  
[Tightening torque: Refer to the following table.  
Loosen and tighten this nut using a double-ended wrench.  
Coat the flare contact surface with refrigerating machine oil (Ester oil, ether oil or  
alkylbenzene [small amount])]  
Keep the ball valve closed until refrigerant charging to the pipes to be  
added on site has been completed. Opening the valve before charging  
the refrigerant may result in unit damage.  
I
J
K
ø15.88 [5/8] (PQRY-P72)  
ø19.05 [3/4] (PQRY-P96)  
ø19.05 [3/4] (PQRY-P72)  
ø22.2 [7/8] (PQRY-P96)  
Do not use a leak detection additive.  
Field piping  
9.3. Airtight test, evacuation,and refrigerant  
charging  
Appropriate tightening torque by torque wrench:  
Copper pipe external dia. (mm [in])  
ø6.35 [1/4]  
Tightening torque (N·m / kg·cm)  
1
Airtight test  
14 to 18 / 140 to 180  
35 to 42 / 350 to 420  
50 to 57.5 / 500 to 575  
75 to 80 / 750 to 800  
100 to 140 / 1000 to 1400  
Perform with the ball valve of the heat source unit closed, and pressurize the  
connection piping and the indoor unit from the service port provided on the ball  
valve of the heat source unit. (Always pressurize from both the high press pipe  
and the low press pipe service ports.)  
ø9.52 [3/8]  
ø12.7 [1/2]  
ø15.88 [5/8]  
ø19.05 [3/4]  
[Fig. 9.3.1] (P.4)  
Tightening angle standard:  
A
D
G
J
Nitrogen gas  
Lo knob  
B
E
H
To indoor unit  
Hi knob  
C
F
I
System analyzer  
Ball valve  
Pipe diameter (mm [in])  
ø6.35 [1/4], ø9.52 [3/8]  
ø12.7 [1/2], ø15.88 [5/8]  
ø19.05 [3/4]  
Tightening angle (°)  
60 to 90  
Low press. pipe  
Service port  
High press. pipe  
Heat source unit  
30 to 60  
20 to 35  
Observe the following restrictions when conducting an air tightness test to prevent  
negative effects on the refrigerating machine oil. Also, with nonazeotropic refriger-  
ant (R410A), gas leakage causes the composition to change and affects perform-  
ance. Therefore, perform the airtightness test cautiously.  
[Fig. 9.2.3] (P.3)  
Note:  
If a torque wrench is not available, use the following method as a standard:  
When you tighten the flare nut with a wrench, you will reach a point where  
the tightening torque will abruptly increase. Turn the flare nut beyond this  
point by the angle shown in the table above.  
Airtight test procedure  
Restriction  
1. Nitrogen gas pressurization  
If a flammable gas or air (oxygen) is used as the pressurization  
gas, it may catch fire or explode.  
(1) After pressurizing to the design pressure (4.15 MPa [601 psi]) using nitrogen gas, allow it to  
stand for about one day. If the pressure does not drop, airtightness is good.  
However, if the pressure drops, since the leaking point is unknown, the following bubble test  
may also be performed.  
(2) After the pressurization described above, spray the flare connection parts, brazed parts, flanges,  
and other parts that may leak with a bubbling agent (Kyuboflex, etc.) and visually check for  
bubbles.  
(3) After the airtight test, wipe off the bubbling agent.  
2. Pressurization using refrigerant gas and nitrogen gas  
Do not use a refrigerant other than that indicated on the unit.  
Sealing with gas from a cylinder will cause the composition of  
the refrigerant in the cylinder to change.  
(1) Pressurizing to a gas pressure of approximately 0.2 MPa [29 psi], pressurize to the design  
pressure (4.15 MPa [601 psi]) using nitrogen gas.  
However, do not pressurize at one time. Stop during pressurization and check that the pres-  
sure does not drop.  
Use a pressure gauge, charging hose, and other parts especially  
for R410A.  
(2) Check for gas leaks by checking the flare connection parts, brazed parts, flanges, and other  
parts which may leak using an R410A compatible electric leak detector.  
(3) This test may be used together the with bubble type gas leak test.  
An electric leak detector for R22 cannot detect leaks of R410A.  
Do not use a haloid torch. (Leaks cannot be detected.)  
Caution:  
Only use refrigerant R410A.  
Use a gauge manifold, charging hose, and other parts for the refrigerant  
indicated on the unit.  
- The use of other refrigerant such as R22 or R407C, which contains chlorine, will  
deteriorate the refrigerating machine oil or cause the compressor to malfunction.  
Use a graviometer. (One that can measure down to 0.1 kg [4 oz].)  
Use a vacuum pump with a reverse flow check valve.  
(Recommended vacuum gauge: ROBINAIR 14830A Thermistor Vacuum  
Gauge)  
2
Evacuation  
Also use a vacuum gauge that reaches 65 Pa [abs] [0.00943 psi/0.5Torr]  
or below after operating for five minutes.  
Evacuate with the ball valve of the heat source unit closed and evacuate both  
the connection piping and the indoor unit from the service port provided on the  
ball valve of the heat source unit using a vacuum pump. (Always evacuate from  
the service port of both the high press pipe and the low press pipe.) After the  
vacuum reaches 650 Pa [abs] [0.0943 psi/5 Torr], continue evacuation for at  
least one hour or more.  
3
Refrigerant Charging  
Since the refrigerant used with the unit is nonazerotropic, it must be charged in  
the liquid state. Consequently, when charging the unit with refrigerant from a  
cylinder, if the cylinder does not have a syphon pipe, charge the liquid refriger-  
ant by turning the cylinder upside-down as shown in Fig.9.3.3. If the cylinder  
has a syphon pipe like that shown in the picture on the right, the liquid refriger-  
ant can be charged with the cylinder standing upright. Therefore, give careful  
attention to the cylinder specifications. If the unit should be charged with gas  
refrigerant, replace all the refrigerant with new refrigerant. Do not use the re-  
frigerant remaining in the cylinder.  
* Never perform air purging using refrigerant.  
[Fig. 9.3.2] (P.4)  
A
D
G
J
M
System analyzer  
Ball valve  
B
E
H
K
N
Lo knob  
C
F
I
L
O
Hi knob  
Low press. pipe  
Three-way joint  
R410A cylinder  
To indoor unit  
High press. pipe  
Valve  
Service port  
Valve  
Scale  
[Fig. 9.3.3] (P.4)  
Vacuum pump  
Heat source unit  
A
Syphon pipe  
B
In case of the cylinder having no syphon pipe.  
Note:  
Always add an appropriate amount of refrigerant. Also always seal the  
system with liquid refrigerant.Too much or too little refrigerant will cause  
trouble.  
11